Probabilistic model for MV spark-gap characteristics with lightning induced overvoltage superimposed on AC voltage
Authors:
- 30 October 2009
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 16 (5) , 1404-1412
Abstract
In this paper, the breakdown probability of MV spark-gaps is modeled using the Gaussian distribution function under an impulse voltage test in accordance with the IEC 60060-1 standard. The model is presented in the form of the well-known Gaussian tail probability. Accordingly, a modified probabilistic model is introduced to study the effect of impulse voltage superimposed on the AC voltage on the breakdown probability of MV spark-gaps. The modified model is verified using experimental data, where the experimental setup is arranged to generate a range of impulse voltages superimposed on the ac voltages. The results show evidence of the efficacy of the proposed probabilistic model. Furthermore, the proposed model is used to evaluate single-phase, two-phase and three-phase spark-gap breakdown probabilities in the case of lightning induced overvoltages. Finally, these breakdown probabilities are used along with the simplified Rusck expression to evaluate the performance of MV overhead lines above a perfectly conducting ground under lightning-induced voltages using a statistical approach.Keywords
This publication has 20 references indexed in Scilit:
- An Approach to the Lightning Overvoltage Protection of Medium Voltage Lines in Severe Lightning AreasAIP Conference Proceedings, 2008
- Development of Arcing Horn Device for Interrupting Ground-Fault Current of 77 kV Overhead LinesIEEE Transactions on Power Delivery, 2005
- Lightning induced voltages on multiconductor power distribution lineIEE Proceedings - Generation, Transmission and Distribution, 2005
- Co-ordination of spark-gap protection with zinc-oxide surge arrestersIEE Proceedings - Generation, Transmission and Distribution, 2001
- Impulse breakdown superposed on ac voltage in XLPE cable insulationIEEE Transactions on Dielectrics and Electrical Insulation, 1996
- Flashover voltage characteristics of contaminated station insulators under temporary ac overvoltages in the ac system connected with a frequency converter stationElectrical Engineering in Japan, 1993
- Dielectric strength of oil-immersed transformer insulation with superimposed AC and lightning impulse voltageIEEE Transactions on Electrical Insulation, 1990
- Development of current limiting arcing horn for prevention of lightning faults on distribution linesIEEE Transactions on Power Delivery, 1988
- A Study of Predischarge Current Characteristics of Long Air GapsIEEE Transactions on Power Apparatus and Systems, 1985
- Partial Discharges Triggered by Switching Surge in Power TransformersIEEE Transactions on Power Apparatus and Systems, 1972