Modeling FACTS Device Impact on Voltage Flicker in the Electric Arc Furnace Supply System
- 1 September 2019
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-4
Abstract
This paper discusses the issue of modeling voltage flicker compensation devices in electric arc furnace power supply system. Simple algorithms of modeling the arc furnace and the compensating device are presented. In the proposed model, the statistical indices of arc furnace active and reactive powers and their harmonic approximation in each time interval of one second are used. Such approach allows us to use the index $\Delta U_{10}$ to estimate the equivalent effect of voltage fluctuations. The most annoying voltage fluctuations are within the frequency range of 1-25 Hz, and the efficiency of compensation devices in EAF power supply systems is dependent by their ability to reduce these fluctuations. The objective of the work is to create a simple tool for comparative assessment of compensation devices impact on voltage flicker in the EAF power supply system.
Keywords
This publication has 4 references indexed in Scilit:
- IEEE Recommended Practice for Measurement and Limits of Voltage Fluctuations and Associated Light Flicker on AC Power Systems2008
- Circuit-level comparison of STATCOM technologiesIEEE Transactions on Power Electronics, 2003
- Voltage flicker mitigation using PWM-based distribution STATCOM2003
- Comparison of thyristor-controlled reactors and voltage-source inverters for compensation of flicker caused by arc furnacesIEEE Transactions on Power Delivery, 2000