Universal pilot relaying scheme for series and shunt‐compensated lines
Open Access
- 17 January 2018
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 12 (4) , 799-806
Abstract
The fault component power and energy‐based relaying schemes find limitation during the double phase to ground faults due to the effect of mutual coupling. In this study, a pilot relaying scheme for series and shunt‐compensated transmission lines is introduced which is based on incremental reactive power coefficients (IRPCs). The IRPC of a phase is defined as the ratio of integrated incremental reactive power (IIRP) to the maximum magnitude of IIRP among all three phases. If IRPC of any phase is found less than −0.5, the internal fault is detected else if none of the phases has IRPC less than −0.5, the fault is an external fault. The algorithm will start only if the incremental differential current of any phase is found >50% of pre‐fault differential current. The proposed scheme has various advantages including universal applicability to protect the series and shunt‐compensated transmission lines. The offline and real‐time simulations are carried out to investigate the performance of the proposed scheme under different operating conditions. The scheme is robust and accurate for all the conditions. Further, the performance of the proposed scheme is superior to the recently proposed schemes.Keywords
This publication has 19 references indexed in Scilit:
- A performance oriented impedance based fault location algorithm for series compensated transmission linesInternational Journal of Electrical Power & Energy Systems, 2015
- An Innovative Directional Relaying Scheme Based on Postfault CurrentIEEE Transactions on Power Delivery, 2014
- Adaptive distance relay setting for series compensated lineInternational Journal of Electrical Power & Energy Systems, 2013
- Series-Compensated Double-Circuit Transmission- Line Protection Using Directions of Current TransientsIEEE Transactions on Power Delivery, 2013
- Directional relaying for double circuit line with series compensationIET Generation, Transmission & Distribution, 2013
- Directional Relaying in the Presence of a Thyristor-Controlled Series CapacitorIEEE Transactions on Power Delivery, 2013
- Transmission-Line Protection: A Directional Comparison Scheme Using the Average of Superimposed ComponentsIEEE Transactions on Power Delivery, 2013
- Impact of SVC on the protection of transmission linesInternational Journal of Electrical Power & Energy Systems, 2012
- Performance Comparison of Distance Protection Schemes for Shunt-FACTS Compensated Transmission LinesIEEE Transactions on Power Delivery, 2007