Induced Voltage-Based Optimization of Grounding Intervals for MV Busbar Enclosures
Open Access
- 19 March 2026
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Access
- Vol. 14, 46170-46177
Abstract
Methods for establishing Medium-voltage (MV) grounding systems, which can be dangerous and costly, are typically based on traditional practices or on unscientific assumptions (e.g., fixed 10–20 meter intervals). Consequently, these methods fail to consider the geometry of conductors and high load currents which can lead to unsafe touch voltages and excessive installation costs. This research establishes a scientifically based method, grounded in the laws of physics and compliant with IEC 60364, for determining grounding connection intervals, and determines the electromagnetic coupling between phase conductors and metal enclosures using measured mutual inductance data and COMSOL Multiphysics simulations. This approach of has enabled the determination of the induced voltage gradients associated with MV busbar connection systems across various current levels (up to 5000 amps) and voltage classes (12-24 kV). Therefore, this research has provided an understanding of the physical characteristics that govern grounding system connections. The results indicate that the maximum safe grounding distances (Lmax), found to range from 120.3 m for 950 A systems to 33.5 m for high-capacity 5000 A systems, depend strongly on system design parameters. The sensitivity analysis indicates that Lmax is most influenced by fluctuations in load current and geometric clearances, and therefore provides practical guidance for incorporating strategic safety multipliers (0.8 and 0.6) into engineering applications. Additionally, this study provides a scalable framework to ensure that all grounding system designs meet the 50 V safety standard while minimizing over-engineering. In addition, this study enables the application of experimental or experience-based knowledge to the design of modern electrical infrastructure, going beyond simple estimates and providing a scientific framework for grounding system designs.Keywords
This publication has 22 references indexed in Scilit:
- Methodology for optimizing electrical grounding grids in stratified soils using advanced calculation techniques and evolutionary algorithmsSwarm and Evolutionary Computation, 2025
- AIEE Guide for Safety in Alternating-Current Substation Grounding2019
- S-parameters-based causal RLGC(f) model of busbar distribution systems for broadband power line communicationInternational Journal of Electrical Power & Energy Systems, 2018
- Multiphysics analysis of busbars with various arrangements under short‐circuit conditionIET Electrical Systems in Transportation, 2016
- Magnetic field of a shielded three-phase busbar system2015
- Study on the electromagnetic force affected by short-circuit current in vertical and horizontal arrangement of busbar system2011
- Analysis of Multiconductor Transmission Lines2007
- Experimental and numerical evaluation of busbar trunking impedanceElectric Power Systems Research, 2000
- Numerical and experimental evaluation of magnetic field generated by power busbar systemsIEE Proceedings - Generation, Transmission and Distribution, 1996
- A simplified approach to calculating current distribution in parallel power busesIEEE Transactions on Magnetics, 1990