Transformer Winding Fault Locating Using Frequency Domain Reflectometry (FDR) Technology
Open Access
- 5 August 2025
- journal article
- research article
- Published by MDPI AG in Electronics
- Vol. 14 (15) , 3117
Abstract
Detecting power transformer winding degradations at an early stage is very important for the safe operation of nuclear power plants. Most transformer failures are caused by insulation breakdown; the winding turn-to-turn short circuit fault is frequently encountered. Experience has shown that routine testing techniques, e.g., winding resistance, leakage inductance, and sweep frequency response analysis (SFRA), are not sensitive enough to identify minor turn-to-turn short defects. The SFRA technique is effective only if the fault is in such a condition that the flux distribution in the core is prominently distorted. This paper proposes the frequency domain reflectometry (FDR) technique for detecting and locating transformer winding defects. FDR measures the wave impedance and its change along the measured windings. The wire over a plane model is selected as the transmission line model for the transformer winding. The effectiveness is verified through lab experiments on a twist pair cable simulating the transformer winding and field testing on a real transformer. The FDR technique successfully identified and located the turn-to-turn short fault that was not detected by other testing techniques. Using FDR as a complementary tool for winding condition assessment will be beneficial.Keywords
This publication has 25 references indexed in Scilit:
- Detection of probability of occurrence, type and severity of faults in transformer using frequency response analysis based numerical indicesMeasurement, 2021
- A Method of Fault Localization Within the Blind Spot Using the Hybridization Between TDR and Wavelet TransformIEEE Sensors Journal, 2020
- Locating Inter-Turn Faults in Transformer Windings Using Isometric Feature Mapping of Frequency Response TracesIEEE Transactions on Industrial Informatics, 2020
- Interpretation of frequency response analysis of power transformer based on evidence theoryIET Generation, Transmission & Distribution, 2019
- Diagnosis and clustering of power transformer winding fault types by cross‐correlation and clustering analysis of FRA resultsIET Generation, Transmission & Distribution, 2018
- Localization of mechanical deformations in transformer windings using time-domain representation of response functionsInternational Transactions on Electrical Energy Systems, 2012
- Determination of Complex Permeability of Silicon Steel for Use in High-Frequency Modeling of Power TransformersIEEE Transactions on Magnetics, 2008
- Exploring Possibilities for Characterization of Power Transformer Insulation by Frequency Response Analysis (FRA)IEEE Transactions on Power Delivery, 2006
- An Effort to Understand What Factors Affect the Transfer Function of a Two-Winding TransformerIEEE Transactions on Power Delivery, 2005
- Transformer Diagnostic Testing by Frequuency Response AnalysisIEEE Transactions on Power Apparatus and Systems, 1978