Enhanced Clustering of DC Partial Discharge Pulses Using Multi-Level Wavelet Decomposition and Principal Component Analysis
Open Access
- 11 September 2025
- Vol. 18 (18) , 4835
Abstract
Partial discharge (PD) is a critical indicator of insulation degradation in high-voltage DC systems, necessitating accurate diagnosis to ensure long-term reliability. Conventional AC-based diagnostic methods, such as phase-resolved partial discharge analysis (PRPDA), are ineffective under DC conditions, emphasizing the need for waveform-based analysis. This study presents a novel clustering framework for DC PD pulses, leveraging multi-level wavelet decomposition and statistical feature extraction. Each signal is decomposed into multiple frequency bands, and 70 distinctive waveform features are extracted from each pulse. To mitigate feature redundancy and enhance clustering performance, principal component analysis (PCA) is employed for dimensionality reduction. Experimental data were obtained from multiple defect types and measurement distances using a 22.9 kV cross-linked polyethylene (XLPE) cable system. The proposed method significantly outperformed conventional time-frequency (T-F) mapping techniques, particularly in scenarios involving signal attenuation and mixed noise. Propagation-induced distortion was effectively addressed through multi-resolution analysis. In addition, field noise sources such as HVDC converter switching transients and fluorescent lamp emissions were included to assess robustness. The results confirmed the framework’s capability to distinguish between multiple PD types and noise sources, even in challenging environments. Furthermore, optimal mother wavelet selection and correlation-based feature analysis contributed to improved clustering resolution. This framework supports robust PD classification in practical HVDC diagnostics. The framework can contribute to the development of real-time autonomous monitoring systems for HVDC infrastructure. Future research will explore incorporating temporal deep learning architectures for automated PD-type recognition based on clustered data.Keywords
Funding Information
- Korea Electrotechnology Research Institute (25A01045)
This publication has 28 references indexed in Scilit:
- Practical aspects of partial discharge measurement for HVDC cablesJournal of Physics D: Applied Physics, 2020
- On-line partial discharge measurement of turbine generators with new noise rejection techniques on pulse-by-pulse basis2002
- Pulse-shape characteristics of partial discharge within electrical trees in polymeric materials2002
- The experimental study on tree growth in XLPE using 3D PD patterns2002
- Partial discharge signal generation transmission and acquisitionIEE Proceedings - Science, Measurement and Technology, 1995
- Computer-aided measurement of partial discharges in HV equipmentIEEE Transactions on Electrical Insulation, 1993
- Evaluation of digital filters for rejecting discrete spectral interference in on-site PD measurementsIEEE Transactions on Electrical Insulation, 1993
- Pattern recognition of partial discharge in XLPE cables using a neural networkIEEE Transactions on Electrical Insulation, 1992
- Discrimination of partial discharge patterns using a neural networkIEEE Transactions on Electrical Insulation, 1992
- Modulation of partial discharge activity in GIS insulators by X-ray irradiationIEEE Transactions on Electrical Insulation, 1991