Adaptive PI + VPI Harmonic Current Compensation Strategy under Weak Grid Conditions
Open Access
- 12 May 2023
- journal article
- research article
- Published by MDPI AG in Applied Sciences
- Vol. 13 (10) , 5983
Abstract
With the increase of the penetration rate of renewable energy power generation in the power system, the power grid gradually tends to be weak. Under the scenario of nonlinear load connecting to weak power grid, the grid-side voltage will produce unbalance, distortion and frequency deviation due to the influence of large internal impedance, insufficient inertia, three-phase current unbalance and harmonics of weak power grid. The operation of active power filters (APF) under above conditions can lead to significant degradation in harmonic compensation performance. An adaptive proportional integral (PI) + vector PI (VPI) harmonic compensation strategy for a three-phase APF is proposed for use in complex conditions of weak grid. The strategy consists of an adaptive notch filter based synchronous phase-locked loop (ANF-PLL) and an adaptive PI + VPI current control method. In this strategy, a series of adaptive lattice notch filters are introduced to improve the accuracy of grid phase and frequency estimation under the condition of voltage unbalance, distortion and a large range of frequency deviation. Then the phase and frequency information are used in the Park transformation of harmonic detection and current compensation control and the update of PI + VPI current control law parameters. A VPI current tracking controller with adaptive resonant frequency is constructed, which can improve the gain of the resonant frequency point and ensure that the APF can maintain the best compensation performance under the above weak grid conditions. Finally, the simulation and experimental results indicate that the ANF-PLL shows a better phase and frequency estimation performance under complex conditions of weak grid than the conventional and notch filter based methods, and the harmonic compensation strategy presented in this paper achieves a significant performance improvement under complex conditions of weak grid compared with Fixed VPI/SRF-PLL strategy and adaptive VPI/NF-PLL strategy.Keywords
Funding Information
- National Natural Science Foundation of China (51467017, 2018MS05026, RC201701)
- Inner Mongolia Natural Science Foundation of China (51467017, 2018MS05026, RC201701)
- Inner Mongolia Autonomous Region Talent Development Project Foundation of China (51467017, 2018MS05026, RC201701)
This publication has 31 references indexed in Scilit:
- An Adaptive Digital-Control Scheme for Improved Active Power Filtering Under Distorted Grid ConditionsIEEE Transactions on Industrial Electronics, 2017
- A Hybrid Filtering Stage Based Quasi-type-1 PLL under Distorted Grid ConditionsJournal of Power Electronics, 2017
- An Improved Control Strategy of Three-Phase PWM Rectifiers Under Input Voltage Distortions and DC-Offset Measurement ErrorsIEEE Journal of Emerging and Selected Topics in Power Electronics, 2017
- A Lyapunov Stability Theory-Based Control Strategy for Three-Level Shunt Active Power FilterEnergies, 2017
- Performance Improvement of Quasi-Type-1 PLL by using a Complex Notch FilterIEEE Access, 2016
- Explicit Phase Lead Filter Design in Repetitive Control for Voltage Harmonic Mitigation of VSI-Based Islanded MicrogridsIEEE Transactions on Industrial Electronics, 2016
- Impedance-Phased Dynamic Control Method for Grid-Connected Inverters in a Weak GridIEEE Transactions on Power Electronics, 2016
- A Robust Synchronization to Enhance the Power Quality of Renewable Energy SystemsIEEE Transactions on Industrial Electronics, 2015
- Robust Control for Microgrid Frequency Deviation Reduction With Attached Storage SystemIEEE Transactions on Smart Grid, 2014