An Analytical Approach to the Heat and Mass Transfer Processes in Counterflow Cooling Towers
Author:
- 9 May 2006
- journal article
- Published by Wiley in Journal of Heat Transfer
- Vol. 128 (11) , 1142-1148
Abstract
Quick and accurate analysis of cooling tower performance, outlet conditions of moist air, and parameter profiles along the tower height is very important in rating and design calculations. This paper developed an analytical model for the coupled heat and mass transfer processes in counterflow cooling towers based on operating conditions more realistic than most conventionally adopted Merkel approximations. In modeling, values of the Lewis factor were not necessarily specified as unity. Effects of water loss by evaporation and water film heat transfer resistance were also considered in the model equations. Within a relatively narrow range of operating conditions, the humidity ratio of air in equilibrium with the water surface was assumed to be a linear function of the surface temperature. The differential equations were rearranged and an analytical solution was developed for newly defined parameters. The analytical model predicts the tower performances, outlet conditions, and parameter profiles quickly and accurately when comparing with the numerical integration of the original differential equations.Keywords
This publication has 10 references indexed in Scilit:
- Cooling Tower Performance Evaluation: Merkel, Poppe, and e-NTU Methods of AnalysisJournal of Engineering for Gas Turbines and Power, 2005
- Temperature profile in countercurrent/cocurrent spray towersInternational Journal of Heat and Mass Transfer, 2001
- An Improved Design and Rating Analyses of Counter Flow Wet Cooling TowersJournal of Heat Transfer, 2001
- Application of a general non-dimensional mathematical model to cooling towersInternational Journal of Thermal Sciences, 1999
- A general mathematical model of evaporative cooling devicesRevue Générale de Thermique, 1998
- A Modified Analysis of Counter Flow Wet Cooling TowersJournal of Heat Transfer, 1997
- On the analysis of counter-flow cooling towersInternational Journal of Heat and Mass Transfer, 1991
- Design of Cooling Towers by the Effectiveness-NTU MethodJournal of Heat Transfer, 1989
- Analysis of Mechanical-Draught Counterflow Air/Water Cooling TowersJournal of Heat Transfer, 1983
- A Comprehensive Approach to the Analysis of Cooling Tower PerformanceJournal of Heat Transfer, 1961