Mathematical model based on the radiosity method for estimating the efficiency of in-duct UVGI systems
- 26 July 2022
- journal article
- research article
- Published by Taylor & Francis in Science and Technology for the Built Environment
- Vol. 28 (9) , 1255-1269
Abstract
The article describes a model for calculating the killing ratio of different pathogens with an in-duct ultraviolet (UV) device. The model is based on the radiosity method adapted for the UV radiation range and can be used for analysing any lamp distribution. The paper provides the necessary view factors and the influence of environmental variables (temperature, humidity and air velocity) in the analysis. The model has been validated using the results of four commercial equipment certificates issued by the US Environmental Protection Agency (EPA). The model results show a high precision on the test results, with a maximum deviation of 9%. In all cases, the model results are lower than that of the test, which allows being on the side of safety in the design. The model has been programmed in software used by Steril-Air for designing its equipment. Finally, an example of calculating the SARS-CoV-2 killing ratio with a 4x2 lamps arrangement is shown.Keywords
This publication has 24 references indexed in Scilit:
- Upper room UVGI effectiveness with dispersed pathogens at different droplet sizes in spaces conditioned by chilled ceiling and mixed displacement ventilation systemBuilding and Environment, 2015
- Improving the effectiveness of ultraviolet germicidal irradiation through reflective wall coatings: Experimental and modeling based assessmentsIndoor and Built Environment, 2014
- Inverse Radiative Heat Transfer2013
- Effect of enhanced ultraviolet germicidal irradiation in the heating ventilation and air conditioning system on ventilator-associated pneumonia in a neonatal intensive care unitJournal of Perinatology, 2011
- Introduction2009
- Modelling the Performance of Upper Room Ultraviolet Germicidal Irradiation Devices in Ventilated Rooms: Comparison of Analytical and CFD MethodsIndoor and Built Environment, 2004
- Effectiveness of Germicidal UV Radiation for Reducing Fungal Contamination within Air-Handling UnitsApplied and Environmental Microbiology, 2001
- Bioaerosols: Prevalence and health effects in the indoor environmentJournal of Allergy and Clinical Immunology, 1990
- Algebraic methods for the calculation of radiation exchange in an enclosureWärme- und Stoffübertragung, 1974
- The Influence of Light upon the Development of Bacteria 1Nature, 1877