Airside Performance of H-Type Finned Tube Banks with Surface Modifications
Open Access
Abstract
The present study numerically investigates some novel modifications to augment the performance of the H-type finned tube banks, which are widely used in waste heat recovery in industries. The imposed modifications upon the original H-type finned tube banks include the following: (1) Design 1 contains some triangular cuts at the edge of the original rectangular fin; (2) Design 2 modifies the original rectangular geometry into a trapezoid shape; (3) Design 3 renders the original rectangular cross-section fin thickness into trapezoid cross-section; and (4) Design 4 changes the original rectangular shape into a circular shape. Based on the simulations, it is found that Design 1 shows barely any improvements in the heat transfer performance and surface area reduction. Design 2 can provide some weight saving and surface area reduction at a slightly inferior heat transfer performance. Design 3 can offer up to 14% improvements in the overall heat transfer performance without any pumping power penalty. Yet, Design 4 provides the maximum weight saving as compared to the original reference case. With 3–9% lesser surface area than the reference case, Design 4 still offers marginally higher heat transfer performance.Keywords
Funding Information
- Ministry of Science and Technology, Taiwan (107-2622-E-009-002-CC2)
This publication has 8 references indexed in Scilit:
- Experimental Study of Heat Transfer and Pressure Drop for H-type Finned Oval Tube with Longitudinal Vortex Generators and Dimples under Flue GasHeat Transfer Engineering, 2017
- Numerical Study of the Solid Particle Erosion on H-Type Finned Circular/Elliptic Tube SurfaceCommunications in Computational Physics, 2017
- Analytical analysis and experimental verification of trapezoidal fin for assessment of heat sink performance and material savingApplied Thermal Engineering, 2016
- A novel trapezoid fin pattern applicable for air-cooled heat sinkHeat and Mass Transfer, 2015
- Experimental Investigation of Heat Transfer and Pressure Drop Characteristics of H-type Finned Tube BanksEnergies, 2014
- Numerical investigation of heat transfer and erosion characteristics for H-type finned oval tube with longitudinal vortex generators and dimplesApplied Energy, 2014
- A novel ‘‘partial bypass” concept to augment the performance of air-cooled heat exchangersInternational Journal of Heat and Mass Transfer, 2012
- Experimental study on the performance of a novel fin-tube air heat exchanger with punched longitudinal vortex generatorEnergy Conversion and Management, 2012