Abstract
The article provides a theoretical substantiation of the aerodynamic characteristics of an indirect evaporative air heat exchanger operating according to the Maisotsenko thermodynamic cycle (M-cycle) and intended for microclimate control systems in livestock buildings. The study is motivated by increasing summer thermal loads, the limited performance of conventional direct adiabatic cooling, and the need to reduce ventilation energy use without increasing the humidity of supply air. A design concept featuring cross-flow interaction of dry and wet air streams is proposed, enabling deep cooling to temperatures close to the ambient dew point. A comprehensive mathematical model for pressure-loss prediction in the heat exchanger channels is developed. The model is based on an analytical decomposition of the airflow path into characteristic sections and accounts for channel geometry, flow regime, and the equivalent roughness of wetted surfaces. Numerical analysis establishes the influence of channel cross-sectional area, number of channels, and airflow velocity on total aerodynamic resistance and required fan power. The channel cross-sectional shape is shown to be a decisive factor for energy performance: for equal cross-sectional areas, circular channels reduce total pressure losses by up to 26% compared with square and triangular channels. The results can be used to optimize the design of indirect evaporative heat exchangers and to improve the energy efficiency of ventilation and air-conditioning systems in livestock buildings.

This publication has 15 references indexed in Scilit: