Implementation and Performance Evaluation of a Reclosing Method for Shunt Reactor-Compensated Transmission Lines
- 3 December 2010
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 26 (2) , 954-962
Abstract
This paper proposes a new control method to reduce overvoltages due to three-phase reclosing for shunt compensated transmission lines (TL). The method detects the first minimum voltage region of the beating across the circuit breakers after protection dead time and works independently of voltage zero crossing, reducing significantly the reclosure time. The controller was tested on a Real Time Digital Simulator (RTDS) and its performance was compared to the traditional preinsertion resistor approach and another existing control method.Keywords
This publication has 6 references indexed in Scilit:
- Mitigation of switching overvoltages in transmission lines via controlled switching2008
- Controlled Switching of HVAC Circuit Breakers: Application Examples and Benefits2008
- Improved EHV line switching surge control by application of MO-arresters and controlled switching2002
- Controlled closing on shunt reactor compensated transmission lines. I. Closing control device developmentIEEE Transactions on Power Delivery, 1997
- Elimination of closing resistors on EHV circuit breakersIEEE Transactions on Power Delivery, 1988
- Accurate Modelling of Frequency-Dependent Transmission Lines in Electromagnetic Transient SimulationsIEEE Transactions on Power Apparatus and Systems, 1982