Abstract
Inverter-interfaced renewable energy sources (IIRESs) are controlled to follow low-voltage ride-through requirements during different fault conditions to support grid voltages and enhance stability. However, these requirements could result in improper operation of conventional protection functions, e.g., phase selection, that are designed based on the fault current characteristics of conventional power systems. In this paper, a dual-current controller (DCC) is designed for IIRESs to allow precise operation of the conventional phase selection method (PSM) while following the positive- and negative-sequence reactive current generation (RCG) requirements imposed by recent grid codes (GCs). First, the negative-sequence current reference is designed to comply with GC requirements and inject the minimum value of negative-sequence-active current that secures a correct operation of phase selection. Subsequently, the positive-sequence-reactive current is designed to comply with RCG requirements and allow injecting the maximum combination of the positive-and negative-sequence currents without hindering the proper operation of PSM or RCG requirements. Comprehensive time-domain simulations verify the effectiveness of the proposed DCC in meeting both PSM and recent RCG requirements during different fault types, resistances, and locations.