Influence of spike defect on the impulse breakdown characteristics of SF6 gas gap in GIS
Authors:
- 10 August 2018
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 25 (4) , 1413-1420
Abstract
By using 1 MV Marx generator and a 220 kV GIS bus, an experiment platform has been established, and a stainless steel needle is applied to simulate spike defect, so as to study the influence of pressure, wave front time and electric field on 50 % breakdown voltage (U 50 ) and voltage-time (V-t) characteristics of SF 6 gas gap with existence of a spike defect on the bus of GIS under double exponential impulse voltage. When wave front time is short, 50% breakdown voltage of the SF 6 gap hardly changes with various pressures, and U 50% -P curve turns to be a hump shape when wave front time increases. However, pressure has no significant effect on V-t characteristics. The slope of V-t characteristics curve is negative when wave front time of applied voltage is short (0.08~0.9μs), and it will turn to be positive when wave front time becomes longer (several ~15μs). A new method to fit these V-t characteristics curves under impulse voltage with longer wave front times is proposed. It is found that 50 % breakdown voltage decreases almost linearly with the increase of electric field non-uniformity factors (f), and V-t characteristics cluster with valley-like profile have been drawn at different f. Dispersion of V-t characteristics cluster reduces and the flat region expands with the increase of f, and minimum value of breakdown voltage of SF 6 gap with spike defect under impulse voltage, which is of guiding significance for engineering, can be obtained.Keywords
This publication has 19 references indexed in Scilit:
- v-t Characteristics using extended disruptive effect model for impulses of varying front timesIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- 3-MV compact very fast transient overvoltage generator for testing ultra-high-voltage gas-insulated switchgearIEEE Electrical Insulation Magazine, 2014
- Ultra high‐voltage gas‐insulated switchgear – a technology milestoneEuropean Transactions on Electrical Power, 2011
- Recent trend and future perspectives in electrical insulation techniques in relation to sulfur hexafluoride (SF6) substitutes for high voltage electric power equipmentIEEE Electrical Insulation Magazine, 2011
- SF 6 breakdown in GISIEE Proceedings - Science, Measurement and Technology, 1996
- GIS insulation co-ordination: on-site tests and dielectric diagnostic techniques. A utility point of viewIEEE Transactions on Power Delivery, 1996
- The mechanism of leader breakdown in electronegative gasesIEEE Transactions on Electrical Insulation, 1989
- Direct measurement of space-charge injection from a needle electrode into dielectricsJournal of Applied Physics, 1986
- Qualitative model of breakdown in SF6in inhomogeneous gapsJournal of Physics D: Applied Physics, 1983