Positive Sequence Impedances of LV Sector-Shaped Cables in the Frequency Range 2 to 9 kHz
- 18 October 2021
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-5
Abstract
The development of modern LV distribution networks is characterized by the growth in the number of converter-interfaced prosumers using electronic elements with switching frequencies in the kHz range. It causes the emission of so-called “supraharmonics” into electrical networks. For the analysis of the propagation of supraharmonics it is necessary to known the corresponding frequency-dependent parameters of LV distribution lines. Modern LV distribution lines are mainly cable lines and designed for the operation at the fundamental frequency (e.g. 50 Hz). The calculation of line impedances at all other frequencies is the subject of special studies. The paper deals with the analysis of positive sequence series impedances of LV sector-shaped cables in the frequency range 2 to 9 kHz. The analysis is based on FEM simulation results. Novel formulas are suggested for the simplified determination of series resistances and inductances of LV 4-core cables with sector-shaped aluminium conductors.Keywords
This publication has 5 references indexed in Scilit:
- Estimation of Power Losses Caused by SupraharmonicsE3S Web of Conferences, 2020
- Calculating Power Losses In LV Cables Loaded With Nonsinusoidal Currents2018
- Cable Parameter Calculation for Typical Industrial Installation Methods and High-Frequency StudiesIEEE Transactions on Industry Applications, 2018
- Series impedance of distribution cables with sector‐shaped conductorsIET Generation, Transmission & Distribution, 2015
- Experimental investigation into harmonic impedance of low-voltage cablesIEE Proceedings - Generation, Transmission and Distribution, 2000