Experimental and numerical study of interactions between sprinklers and natural smoke vents

Authors:

Abstract
Real scale experimentations have been conducted in order to investigate interactions that may occur in a compartment where sprinklers and Smoke and Heat Exhaust Vent Systems coexist. Fuel oil spray was used as fire source with steady heat release rate of 400 and 800 kW. Both sprinkler system and natural Smoke and Heat Exhaust Vent Systems were designed according to the French standards. Effect of vent on sprinkler activation time was studied. An analysis of the temperature field inside the compartment was conducted while vent was opened prior or after sprinkler activation. Simulations of the experiments were also carried out with Fire Dynamics Simulator v.6 for validation purpose and also to provide supplementary data regarding soot flow rate and energy extracted at the vent.

This publication has 7 references indexed in Scilit: