Abstract
This paper presents a modified peak-detection algorithm based control theory for three-phase, three-wire (3P-3W) Shunt Active Power Filter (SAPF) where Cascaded H-Bridge Multilevel Inverter (CHB-MLI) is used as a voltage source inverter (VSI) unit for reactive power compensation, power factor correction and harmonic mitigation in medium-voltage and high-power distribution system. The proposed control theory is implemented in MATLAB/Simulink platform and a rigorous comparative analysis is done with well known p-q theory and synchronous reference frame (SRF) theory to prove its effectiveness. Comparative study shows that modified control algorithm gives better transient performance in terms of settling time and peak overshoot.

This publication has 13 references indexed in Scilit: