Reducing Air‐Conditioning Load by Using an Insulating Material in Iraq as a Case Study (Experimental and Numerical)
- 6 January 2025
- journal article
- research article
- Published by Wiley in Heat Transfer
- Vol. 54 (3) , 2049-2062
Abstract
This paper has studied different types of walls using constant interior and exterior finishing materials (thermostone, 200‐mm thick (A); fired clay bricks, 240‐mm thick (B); hollow concrete blocks, 200‐mm thick (C); solid concrete blocks, 140‐mm thick (D); and limestone, 200‐mm thick (E)) due to the availability of many different types of building materials in Iraq and the lack of control over the best use to demonstrate how each of these materials affects a building's insulation to deliver the appropriate levels of comfort and achieve the greatest possible reduction in the electrical energy needed for air conditioning. A unique chamber was created for performing the actual trials on such walls in their natural environment, which was the climate of the city of Baghdad (zip code 10016, 33° N latitude, 44° E longitude). The tests have been done both in their current state of operation and with the addition of thermal insulation (60‐mm thick microfiber glass insulation material). The values for electricity consumption by a wall without insulation are 92, 121, 199, 148, and 138 kW/m2, in cases noted as A1, B1, C1, D1, and E1, respectively. However, when the insulator is used, the values become 58, 63, 51, 100, and 92 kW/m2 for the cases noted as A2, B2, C2, D2, and E2, respectively. The percentage reduction in electrical energy consumed by the air conditioner used within the room with and without thermal insulation has been recorded in the range of 50%–65% and 25%–60%, respectively. Depending on the model used, and compared with the traditional model, the saving difference with and without insulation was 15% and 35%, respectively. The best case is C2, because it has no effect on the room's interior area. Also, the cooling load was less than in other cases; it was 51 kW/m2 and had the highest building electrical savings, which are 65% when taking the wall in case C1 as a reference.Keywords
All Related Versions
This publication has 36 references indexed in Scilit:
- Reducing heat gain from sheet metal‐clad walls by utilizing industrially wasted materials (experimental study)Heat Transfer, 2023
- Performance of recycled Bakelite plastic waste as eco-friendly aggregate in the concrete beamsCase Studies in Construction Materials, 2023
- Use of waste husk from millet grain cultivation in the production of fired clay bricksInternational Journal of Ceramic Engineering & Science, 2023
- Investigation of Thermal and Strength Properties of a Novel Composite Developed for Insulation as Building MaterialInternational Journal of Thermophysics, 2020
- Development and characterization of thermal insulation materials from renewable resourcesConstruction and Building Materials, 2019
- Green facade for energy savings in buildings: The influence of leaf area index and facade orientation on the shadow effectApplied Energy, 2017
- Affordable construction towards sustainable buildings: review on embodied energy in building materialsCurrent Opinion in Environmental Sustainability, 2013
- Strength and thermal conductivity in lightweight building materialsBulletin of Engineering Geology and the Environment, 2008
- The selection of building material for wall construction by antsAnimal Behaviour, 2007
- Periodic solution of transient heat flow through multilayer walls and flat roofs by complex finite Fourier transform techniqueBuilding and Environment, 2005