Abstract
It is common for 3-level Neutral Point Clamped (NPC) bridges to incorporate a capacitive voltage divider on their DC side. When the two capacitors are identical, the total DC voltage is evenly distributed between them. However, in practice, without corrective measures, the DC capacitor voltages deviate from their nominal values as soon as the system starts exchanging power. This voltage drift occurs during both steady state and transient conditions. Balanced DC voltages are crucial for the proper functioning of the NPC converter, which is why various methods have been proposed in the literature to address the voltage drift problem. In this study, we present a different solution to the capacitor voltage drift problem that does not need any external hardware, and instead uses the switch modulating waveforms to correct the voltages. The effectiveness of this approach is demonstrated by time domain simulations on an active front end converter that exchanges variable amounts of active and reactive powers with the grid.