Comparative analysis of air-to-water and ground source heat pumps performances
- 23 July 2020
- journal article
- research article
- Published by Taylor & Francis in International Journal of Sustainable Energy
- Vol. 40 (1) , 69-84
Abstract
A comparative analysis of the Coefficient of Performance (COP) and the Energy Efficiency Ratio (EER), based on the technical data of 430 different models of air-to-water heat pumps (AWHPs) as well ground-source heat pumps (GSHPs), at certain conditions of ambient air, ground source and water outlet from the heat pump (HP) temperatures, is performed. The results, presented in graphical and tabular form, give the COP and EER values against the HPs nominal capacity and the correlation between COP and EER with the temperature rise ΔΤ along the HP. By averaging the performance values of all AWHPs or GSHPs models, equations of polynomial regression that give the relationship between average COP or EER and ΔΤ values were also calculated. It is shown that inverter-driven HPs generally have higher COP and EER as compared to the fix-capacity HPs, for the same heating or cooling range. Also, performance is highly depended on ΔΤ.Keywords
This publication has 28 references indexed in Scilit:
- On-off cycling losses of reversible air-to-water heat pump systems as a function of the unit power modulation capacityEnergy Conversion and Management, 2019
- Investigation on advanced heat pump systems with improved energy efficiencyEnergy Conversion and Management, 2019
- Operational behavior characteristics and energy saving potential of vertical closed loop ground source heat pump system combined with storage tank in an office buildingEnergy and Buildings, 2018
- Review on sorption materials and technologies for heat pumps and thermal energy storageRenewable Energy, 2017
- Sizing effects on the energy performance of reversible air-source heat pumps for office buildingsApplied Thermal Engineering, 2017
- Improving the energy efficiency of ground-source heat pump systems in heating dominated school buildings: A case study in BelgiumEnergy and Buildings, 2017
- Seasonal performance evaluation of electric air-to-water heat pump systemsApplied Thermal Engineering, 2015
- Evaluation of the economic and environmental feasibility of heat pump systems in residential buildings, with varying qualities of the building envelopeRenewable Energy, 2015
- Energy efficiency in a ground source heat pump with variable speed drivesEnergy and Buildings, 2015
- Simulation study on supply temperature optimization in domestic heat pump systemsBuilding and Environment, 2013