Coupled Harmonic Admittance Identification Based on Least Square Estimation
Open Access
- 29 September 2018
- Vol. 11 (10) , 2600
Abstract
Norton equivalent circuit is a commonly used model in estimating harmonic current emissions of harmonic sources. It however cannot reflect the mutual coupling relationships among voltage and current in different harmonic orders. This paper proposes a new method to identify parameters in a coupled harmonic admittance model. The proposed method is conducted using voltage and current measurements and is based on least square estimation technique. The effectiveness of the method is verified through time-domain simulations for a grid-connected converter and also through field data obtained from a ±800 kV converter station. The experimental results showed that the proposed method presents higher accuracy in terms of harmonic current emission estimation compared with three Norton-base methods.Keywords
Funding Information
- State Grid Corporation of China (GEIRI-DL-71-17-002)
This publication has 35 references indexed in Scilit:
- Impedance Analysis of Modular Multi-Level Converters Connected to Weak AC GridsIEEE Transactions on Power Systems, 2017
- Identification of Harmonic Current Contributions of Iron and Steel Plants Based on Time-Synchronized Field Measurements—Part II: Inside PlantsIEEE Transactions on Industry Applications, 2014
- Identification of Harmonic Current Contributions of Iron and Steel Plants Based on Time-Synchronized Field Measurements—Part I: At PCCIEEE Transactions on Industry Applications, 2014
- A new vector draft method for harmonic source detection at point of common coupling2014
- Modeling and analysis of harmonic resonance in a power electronics based AC power system2013
- Harmonic Analysis in Frequency and Time DomainIEEE Transactions on Power Delivery, 2013
- Modeling of Step-up Grid-Connected Photovoltaic Systems for Control PurposesEnergies, 2012
- Measurement Based on the "Group Linear Regression Method" of Harmonic ImpedanceAdvanced Materials Research, 2011
- A Single Point Measurement Method for Evaluating Harmonic Contributions of Utility and Customer in Power Distribution SystemsJournal of Applied Sciences, 2011
- Harmonic source estimation: A new approach for the localization of nonlinear loads2008