An Experimental Study of In-Tube Condensation and Evaporation Using Enhanced Heat Transfer (EHT) Tubes
Open Access
Abstract
A study was carried out to determine in-tube evaporation and condensation performance of enhanced heat transfer tubes (EHT) using R410A, with the results being compared to a plain tube. The test tubes considered in the evaluation include: plain, herringbone (HB) and spiral (HX) microgrooves, herringbone dimple (HB/D), and hydrophobic herringbone (HB/HY). Experiments to evaluate the condensation were conducted at a saturation of 318 K, and at 279 K for evaporation. Mass flux (G) ranged between 40 to 230 kg m−2s−1. Condensed vapor mass decreased from 0.8 to 0.2; and the mass of vaporized vapor increases from 0.2 to 0.8; heat flux increased with G. Inlet and outlet two-phase flow patterns at 200 kg m−2s−1 were recorded and analyzed. Enhanced tube heat transfer condensation performance (compared to a plain tube) increased in the range from 40% to 73%. The largest heat transfer increase is produced by the herringbone–dimple tube (HB/D). In addition to providing drainage, the herringbone groove also helps to lift the accumulated condensate to wet the surrounding wall. Evaporation thermal performance of the enhanced tubes are from 4% to 46% larger than that of smooth tube with the best performance being in the hydrophobic herringbone tube (HB/HY). This enhancement can be attributed to an increase in the number of nucleation sites and a larger heat transfer surface area. Evaporation and condensation correlations for heat transfer in smooth tubes is discussed and compared.Keywords
This publication has 35 references indexed in Scilit:
- Experimental investigation of condensation in micro-fin tubes of different geometriesExperimental Thermal and Fluid Science, 2012
- Heat transfer and hydrodynamics analysis of a novel dimpled tubeExperimental Thermal and Fluid Science, 2010
- Condensation in Horizontal Smooth Tubes: A New Heat Transfer Model for Heat Exchanger DesignHeat Transfer Engineering, 2006
- Heat transfer and pressure drop for low Reynolds turbulent flow in helically dimpled tubesInternational Journal of Heat and Mass Transfer, 2002
- Condensation of Refrigerants HCFC 22, HFC 134a and HCFC 123 in a Horizontal Smooth Tube. 2nd Report, Proposals of Empirical Expressions for Local Heat Transfer Coefficient.TRANSACTIONS OF THE JAPAN SOCIETY OF MECHANICAL ENGINEERS Series B, 1994
- A general correlation for saturated and subcooled flow boiling in tubes and annuli, based on a nucleate pool boiling equationInternational Journal of Heat and Mass Transfer, 1991
- Describing the uncertainties in experimental resultsExperimental Thermal and Fluid Science, 1988
- A general correlation for flow boiling in tubes and annuliInternational Journal of Heat and Mass Transfer, 1986
- A general correlation for heat transfer during film condensation inside pipesInternational Journal of Heat and Mass Transfer, 1979
- Calculation of void volume fraction in the subcooled and quality boiling regionsInternational Journal of Heat and Mass Transfer, 1970