Sub‐synchronous torsional interaction with VSC‐HVDC affected by feed‐forward compensations in current controllers

Authors:

Abstract
The sub‐synchronous torsional interaction (SSTI) behaviour between turbine‐generator units and the high‐voltage direct current (HVDC) systems has been a vital research content in power systems. In the past, the characteristics of SSTI with line‐commutated‐converter (LCC)‐HVDC have already been well studied. With the development of voltage source converter (VSC)‐based HVDC, some researchers have found that different control parameters of the converter have an impact on the electrical damping of the connected synchronous generator system. However, the existing results did not show the specific mechanism of SSTI. In this study, SSTI with VSC‐HVDC affected by voltage feed‐forward (VVF) compensations in the AC current controllers is investigated. The effects of the asymmetric VVF in both d ‐ and q ‐axes on electrical damping are paid special attention. First, a general output impedance model of VSC‐HVDC concentrated on AC current controllers is developed. Then the influence of compensation factor ( k d/q ) and filter bandwidth ( α f d/q ) on the bandwidth of the converter and the electrical damping is studied. Finally, an SSTI suppression scheme based on the former analysis is given. Simulation studies are carried out in PSCAD/EMTDC, and simulated results validate the analytical results and proposed suppression scheme.