Power Differential Protection for Transformer Based on Fault Component Network
- 13 February 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 38 (4) , 2464-2477
Abstract
Current differential protection has been widely used as the primary protection of transformers. However, inrush currents during transformer energization can cause misoperation of the protection when the second harmonic restraint algorithm fails. This paper proposes a power differential protection scheme based on the fault component network (FCN), which is free from inrush detection and computationally cheap. First, the fault component differential power (FCDP), defined as the differential active power of a transformer in the FCN, is analyzed under different conditions. Second, a transformer protection scheme is presented based on the FCDP and the traditional differential power. A removal algorithm of decaying direct current (DDC) offset is developed to accurately estimate the FCDP. The performance of the scheme is tested under various conditions, including internal faults, external faults and transformer energization. The simulations using PSCAD, and Real Time Digital Simulator (RTDS), experiments in the Electrical Power Dynamic Laboratory (EPDL) and real recording data validate that the proposed method can protect the transformer reliably.Keywords
Funding Information
- National Natural Science Foundation of China (51877127, ZR2022ME097)
- Shandong Provincial Natural Science Foundation of China
This publication has 36 references indexed in Scilit:
- Discriminating transformer large inrush currents from fault currentsInternational Journal of Electrical Power & Energy Systems, 2016
- Improved Online Monitoring Method for Transformer Winding Deformations Based on the Lissajous Graphical Analysis of Voltage and CurrentIEEE Transactions on Power Delivery, 2015
- Protection of transmission lines using fault component integrated powerIET Generation, Transmission & Distribution, 2014
- A Differential Relay for Power Transformers Using Intelligent ToolsIEEE Transactions on Power Systems, 2006
- Assessing and Limiting Impact of Transformer Inrush Current on Power QualityIEEE Transactions on Power Delivery, 2006
- An Equivalent Instantaneous Inductance-Based Technique for Discrimination Between Inrush Current and Internal Faults in Power TransformersIEEE Transactions on Power Delivery, 2005
- Investigation of Power Differential Concept for Line ProtectionIEEE Transactions on Power Delivery, 2005
- Power based differential protection for three phase transformers2003
- Power differential method for discrimination between fault and magnetizing inrush current in transformersIEEE Transactions on Power Delivery, 1997
- A multi-criteria differential transformer relay based on fuzzy logicIEEE Transactions on Power Delivery, 1995