This study presents an inverse hyperbolic secant function based islanding detection technique for distribution network containing various types of distributed generations. The proposed scheme is based on rate of change of inverse hyperbolic secant function of negative sequence voltage signal. Different non‐islanding events along with various islanding conditions have been simulated by modelling IEEE 34‐bus system using PSCAD/EMTDC software package. The proposed scheme is able to detect islanding condition even with zero active and reactive power mismatches. Moreover, it eliminates non‐detection zone completely and at the same time also remains stable during diversified non‐islanding events including change in network topology. The simulation results indicate that the proposed scheme not only detects islanding condition rapidly, but also provides better stability in case of critical non‐islanding events during which most of the existing schemes issue nuisance tripping. Furthermore, comparative evaluation of the proposed scheme with the recently proposed techniques in the literature clearly indicates superiority of the proposed scheme. At the end, issues related to practical implementation of the proposed scheme have also been discussed.Keywords
This publication has 21 references indexed in Scilit:
- A New Rate of Change of Impedance-based Islanding Detection Scheme in Presence of Distributed GenerationElectric Power Components and Systems, 2014
- A new passive islanding detection method and its performance evaluation for multi-DG systemsElectric Power Systems Research, 2014
- Development of EN50438 compliant wavelet-based islanding detection technique for three-phase static distributed generation systemsIET Renewable Power Generation, 2012
- Time-frequency transform-based islanding detection in distributed generationIET Renewable Power Generation, 2011
- A Hybrid Islanding Detection Technique Using Average Rate of Voltage Change and Real Power ShiftIEEE Transactions on Power Delivery, 2009
- A Power Line Signaling Based Technique for Anti-Islanding Protection of Distributed Generators—Part I: Scheme and AnalysisIEEE Transactions on Power Delivery, 2007
- A Power Line Signaling Based Scheme for Anti-Islanding Protection of Distributed Generators—Part II: Field Test ResultsIEEE Transactions on Power Delivery, 2007
- A Hybrid Islanding Detection Technique Using Voltage Unbalance and Frequency Set PointIEEE Transactions on Power Systems, 2007
- Performance of Frequency Relays for Distributed Generation ProtectionIEEE Transactions on Power Delivery, 2006
- Comparative Analysis Between ROCOF and Vector Surge Relays for Distributed Generation ApplicationsIEEE Transactions on Power Delivery, 2005