Research on Steady‐State Thermal Behavior ofSF6/N2andCF3I/N2Mixtures in High Voltage Gas‐Insulated Lines (GIL)
Authors:
- 23 February 2021
- journal article
- research article
- Published by Wiley in IEEJ Transactions on Electrical and Electronic Engineering
- Vol. 16 (4) , 511-518
Abstract
Gas‐insulated lines (GIL) are widely used due to their many advantages in power plants and substations. The security and reliability of GIL is achieved by continues testing and monitoring. The main fault in the GIL compartments is overheating, which is rarely to occur, nonetheless, it cannot be ignored. In the present study, GIL steady‐state thermal behavior was investigated. For this reason, a multiphysics finite element model (FEM) was built to analyze the magneto‐hydro‐thermal characteristics of the GIL insulation gas. The simulation coupling includes the electromagnetic field, flow field and thermal heat transfer field. SF6/N2and CF3I/N2mixtures were studied and the influence of different gas properties on the magnetic flux density, heat distribution and flow velocity had been investigated. The results were compared to an experimental setup to validate the model calculations. Temperature rise tests have been conducted on the GIL inner and outer shell. The measurements were in good agreement with the simulation results. Finally, the presented work is also to serve as a good reference in future design and optimization of GIL structure. © 2021 Institute of Electrical Engineers of Japan. Published by Wiley Periodicals LLC.Keywords
This publication has 26 references indexed in Scilit:
- SF6 concentration sensor for gas-insulated electrical switchgearSensors and Actuators A: Physical, 2014
- Study of gas insulated substation and its comparison with air insulated substationInternational Journal of Electrical Power & Energy Systems, 2014
- Electric Field Characteristics Inside Three-phase Gas Insulated Switchgear in the Presence of Foreign Metallic ParticleProcedia Technology, 2013
- Three-Dimensional Multiphysics Coupled Field Analysis of an Integrated Thermoelectric DeviceNumerical Heat Transfer, Part A: Applications, 2012
- Transport properties of CF3I thermal plasmas mixed with CO2, air or N2 as an alternative to SF6 plasmas in high-voltage circuit breakersJournal of Physics D: Applied Physics, 2011
- Calculation of Temperature Rise in Gas Insulated Busbar by Coupled Magneto-Thermal-Fluid AnalysisJournal of Electrical Engineering & Technology, 2009
- Thermodynamic, transport and radiation properties of high‐temperature CF3I and transient conductance of residual arc sustained in axial CF3I flowIEEJ Transactions on Electrical and Electronic Engineering, 2006
- Kyoto Protocol to the United Nations Framework Convention on Climate ChangeReview of European Community & International Environmental Law, 1998
- Analysis of electromagnetic and thermal fields for a bus duct systemElectric Power Systems Research, 1998
- SF/sub 6//N/sub 2/ mixtures: basic and HV insulation propertiesIEEE Transactions on Dielectrics and Electrical Insulation, 1995