Abstract
This paper presents a robust and adaptive out-of-step (OOS) protection algorithm, using wide-area information, that can be applied on tie-lines in observable power systems. The developed algorithm is based upon real-time computation of the system impedance and makes use of the well-known power-angle characteristic. In this way, a setting-less OOS concept in real-time environment is developed, which is applicable for tie-lines in an arbitrary power system. Furthermore, the developed protection algorithm is installed on hardware and is verified by numerous tests. The performance of the new hardware implementation is compared to the traditional impedance-based OOS protection methods. The results confirm that the proposed algorithm detects OOS conditions faster and more reliably than the traditional impedance-based solutions.
Funding Information
  • SA Archimedes Foundation Kristjan Jaak Scholarship (16-3.5/1470)
  • Esi-Bida and ReSident Project by the Dutch Scientific Council De Nederlandse Organisatie voor Wetenschappelijk Onderzoek (647.003.004)
  • Project and the Consortium Consisting of Transmission System Operator (TSO) TenneT, Distribution System Operators (DSOs) Alliander-Qirion, Stedin, Enduris, and General Electric and VSL

This publication has 27 references indexed in Scilit: