Abstract
Reverse power flow (RPF) from distributed photovoltaic (PV) generation in low-voltage (LV) radial feeders threatens voltage regulation, transformer aging, and unidirectional protection. This paper presents a per-phase time-domain co-simulation platform that couples a procedural network generator, a Markov-chain irradiance model, ComStock/ResStock load profiles, a hybrid prosumer model with behind-the-meter battery storage, and a three-phase pandapower load-flow solver under Mosaik 3. A 432-scenario sweep (3 PV levels × 12 storage capacities × 12 seeds, 30 days at 15 min) shows that PV penetration is the dominant driver of RPF severity: the per-phase inversion time fraction rises from 13.0% to 35.4% as PV scales from 5 to 20 kWh per branch. Behind-the-meter storage is effective at moderate penetration but insufficient at high penetration: even 100 kWh reduces the inversion time fraction by only 29.4% at 20 kW. Root-cause analysis identifies two mechanisms invisible to aggregate steady-state models: households that produce more than they consume on average, and per-phase transformer imbalance. Storage shifts the composition of RPF, absorbing the aggregate surplus while exposing the phase-imbalance floor. Effective RPF elimination, therefore, requires simultaneously addressing both allocation-level and phase-level imbalance.