Abstract
High values and uneven distribution of the transient ground potential rise (TGPR) at the grounding grid conductors in some cases of lightning can disrupt system safety and reliability. To assess the transient performance of grounding grids under lightning currents, a parametric analysis was performed with a computer simulation of 13,978 cases of time-domain responses with parameters in broad ranges. From this study, graphs of impulse impedance and a new formula for the effective area have been developed. The graphs are general; they are for grids of any shape and size and depend on three parameters: the grid conductor spacing, the resistivity of earth, and the zero-to-peak time of the lightning current pulse. In this paper, they are used in a simple procedure to estimate the effectiveness of a mitigation measure to reduce TGPR by increasing the grounding grid mesh density in a limited area around current injection points. Although the parametric analysis was based on a uniform soil model, the graphs can also be used for the two-layer soil model. The procedure is compared with experimental results and its application and limitations are illustrated in examples of large grounding grids.