Stator Current Harmonic Control With Resonant Controller for Doubly Fed Induction Generator
Authors:
- 1 July 2012
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 27 (7) , 3207-3220
Abstract
Voltage harmonics in the grid can introduce stator current harmonics in a doubly fed induction generator (DFIG) wind turbine system, which may potentially impact the generated power quality. Therefore, wind turbine current controllers need to be designed to eliminate the impact of grid voltage harmonics, especially low-order harmonics. This paper proposes a stator current harmonic suppression method using a sixth-order resonant controller to eliminate negative sequence fifth- and positive sequence seventh-order current harmonics. A stator current harmonic control loop is added to the conventional rotor current control loop for harmonic suppression. The overall control scheme is implemented in dq frame. Based on a mathematical model of the DFIG control system, the effects on system stability using the resonant controller, an analysis of the steady-state error, and the dynamic performance, are discussed in this paper. Taking these effects into account, the parameters of the resonant controller can be designed and effectively damp the influence from the grid voltage harmonics. As a result, the impacts of the negative sequence fifth- and positive sequence seventh-order voltage harmonics on the stator current as well as the electromagnetic torque are effectively removed. Simulations and experiments are presented to validate the theoretical analysis.Keywords
This publication has 26 references indexed in Scilit:
- Dynamic Modeling and Improved Control of DFIG Under Distorted Grid Voltage ConditionsIEEE Transactions on Energy Conversion, 2010
- Flexible control of DC-link voltage for doubly fed induction generator during grid voltage swell2010
- Effects of Voltage Unbalance and System Harmonics on the Performance of Doubly Fed Induction Wind GeneratorsIEEE Transactions on Industry Applications, 2010
- Harmonic Analysis of a DFIG for a Wind Energy Conversion SystemIEEE Transactions on Energy Conversion, 2009
- Improved Control of DFIG Systems During Network Unbalance Using PI–R Current RegulatorsIEEE Transactions on Industrial Electronics, 2008
- Rotor Current Controller with Voltage Harmonics Compensation for a DFIG Operating under Unbalanced and Distorted Stator Voltage2007
- Proportional-resonant controllers and filters for grid-connected voltage-source convertersIEE Proceedings - Electric Power Applications, 2006
- Multiple harmonics control for three-phase grid converter systems with the use of PI-RES current controller in a rotating frameIEEE Transactions on Power Electronics, 2006
- SPLL design to flux oriented of a VSC interface for wind power applications2005
- High-Performance Harmonic Extraction Algorithm for a 25 kV Traction Power Quality ConditionerIEE Proceedings - Electric Power Applications, 2004