Abstract
In this paper, three methods based on harmonic resonance mode analysis are proposed for placing PQMs to monitor all harmonic resonance conditions in a power system. These methods compute the optimal number and sites of PQMs for varied load profiles and network configurations such that all harmonic resonance conditions would be monitored. This paper introduces the harmonic resonance severity index that enables electric network owners to place PQMs in a way to monitor only worst‐case harmonic resonance conditions. Also, in this paper, the harmonic resonance observability index is introduced, enabling electrical owners to afford suitable numbers of PQMs based on their budget limitations. The efficiency of the proposed methods has been examined on test systems. The results indicate that using the proposed approach, all harmonic resonance conditions can be captured with an optimal number of PQMs. The proposed approaches also operate with system uncertainties present, which overcomes one of the major weaknesses of the prior approaches. It observes the bus voltage if either this bus or one of the adjacent buses is equipped with at least one PMQ, reduces the number of PQMs, and rearranges their locations to develop a cost‐effective strategy, addressing a long‐standing challenge.Keywords
This publication has 25 references indexed in Scilit:
- Optimal harmonic resonance monitoring in electrical network considering area of harmonic pollution and system uncertaintyIET Generation, Transmission & Distribution, 2024
- Optimal allocation of power quality monitors considering short-duration voltage variations and parallel harmonic resonance conditions in power distribution systemsInternational Journal of Electrical Power & Energy Systems, 2022
- Optimal power quality monitor placement to ensure reliable monitoring of sensitive loads in the presence of voltage sags and harmonic resonances conditionsElectric Power Systems Research, 2022
- Improved modal sensitivity analysis-based method for harmonic resonance analysisElectric Power Systems Research, 2021
- Optimal network reconfiguration for power loss minimization and voltage profile enhancement in distribution systemsHeliyon, 2020
- Dynamic and multi-objective reconfiguration of distribution network using a novel hybrid algorithm with parallel processing capabilityApplied Soft Computing, 2020
- An improved cuckoo search algorithm for the problem of electric distribution network reconfigurationApplied Soft Computing, 2019
- Power quality monitor placement in power systems considering channel limits and estimation error at unobservable buses using a bi-level approachInternational Journal of Electrical Power & Energy Systems, 2018
- Multiobjective optimization for power quality monitoring allocation considering voltage sags in distribution systemsInternational Journal of Electrical Power & Energy Systems, 2018
- Optimal power quality monitor placement using genetic algorithm and Mallow’s CpInternational Journal of Electrical Power & Energy Systems, 2013