Establishing patterns in reducing fire-dangerous properties of sip panels fire-protected with reactive coating
Open Access
- 28 February 2024
- journal article
- research article
- Published by Private Company Technology Center in Eastern-European Journal of Enterprise Technologies
- Vol. 1 (10 (127)) , 47-54
Abstract
An issue related to using SIP panels for building structures is to ensure their stability and durability during operation in wide ranges. Therefore, the object of research was the change in the properties of wood-polymer material in case of fire and its protection when applied with a reactive coating capable of forming a pinocoke layer under the influence of high temperature on the coating. It has been proven that in the process of thermal action on the fire-resistant coating, the heat insulation process of SIP panels involves the formation of soot-like products on the surface of the material. Thus, under the action of the radiation panel on the surface of the OSB sample, after 120 s of thermal exposure, the process of intensive formation of a layer of foam coke, which thermally insulated the wood-polymer material, began; instead, after the radiation panel was exposed to the fire-resistant polystyrene foam sample, the process of destruction began at a temperature of about 100 °C polystyrene foam. When determining the flammability of a fire-resistant SIP panel, it was established that the temperature of the flue gases during the tests was no more than 110 °C, the length of the damaged sample did not exceed 460 mm. At the same time, the mass loss did not exceed 200 g, and independent combustion of the SIP panel sample did not occur despite the high temperature. According to these data, the SIP panel, fire-resistant with a reaction coating, belongs to group G1 (low flammability) and is a non-flammable material. The practical significance is that the results were taken into account during the design of buildings from SIP panels. So, there are reasons to assert the possibility of targeted regulation of the fire protection processes of SIP panels through the use of reactive coatings capable of forming a protective layer on the surface of the material that inhibits the rate of heat transferKeywords
This publication has 18 references indexed in Scilit:
- Active protection against fire: Enhancing the flame retardancy of sandwich panels using an expandable graphite layer formationInternational Journal of Thermal Sciences, 2023
- Polystyrene Foams: Materials, Technology, and Applications2023
- Research of the process of fire protection of cellulose-containing material with intumescent coatingsAIP Conference Proceedings, 2023
- Comparative experimental analysis of the fire resistance of sandwich panels with polyisocyanourate core reinforced with fiberglass fabricCase Studies in Thermal Engineering, 2022
- Fire resistance behaviour of GFRP-polyurethane composite sandwich panels for building floorsComposites Part B: Engineering, 2021
- Comparison of the fire resistance behaviour of structural insulated panels with expanded polystyrene core treated with intumescent coatingJournal of Materials Research and Technology, 2021
- Temperature analysis of steel structures protected by intumescent paint with steel claddings in fireFire and Materials, 2020
- Assessing the structural integrity of carbon-fibre sandwich panels in fire: Bench-scale approachComposites Part B: Engineering, 2019
- Mass loss and flammability of insulation materials used in sandwich panels during the pre‐flashover phase of fireFire and Materials, 2017
- Full-scale natural fire tests on gypsum lined structural insulated panel (SIP) and engineered floor joist assembliesFire Safety Journal, 2011