Abstract
Electrochemical impedance spectroscopy (EIS) enables critical battery state estimation, yet conventional techniques require idle-time harmonic injection, distorting grid waveforms during operation and precluding real-time monitoring. To resolve this limitation, this paper proposes a novel current modulation method for online EIS measurement in cascaded energy storage systems (CHB-BESS). By exploiting the time-frequency duality principle (where time-domain multiplication corresponds to frequency-domain convolution), the proposed method generates target excitation frequencies through real-time current modulation in energy storage converter legs. This approach seamlessly integrates with the nearest level modulation (NLM) strategy of cascaded H-bridge systems, enabling online EIS measuring during normal operation – all while eliminating operational disruption and maintaining grid-side waveform integrity. Validation in MATLAB/Simulink and a down-scaled H-bridge prototype confirms the feasibility of the proposed method, demonstrating disturbance-free operation during normal system functioning while achieving multi-frequency EIS measurements with a mean average percentage error (MAPE) below 2.53%.
Funding Information
  • National Natural Science Foundation of China (52577208)
  • Digital Grid Research Foundation of China Southern Power Grid (DPGCSG-2024-KF-31)

This publication has 30 references indexed in Scilit: