Coherence‐based integrated detection and assessment algorithm for voltages and currents unbalance/disturbance in three‐phase synchronous generators: A validation of simulation results
Open Access
- 9 May 2023
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in The Journal of Engineering
- Vol. 2023 (5)
Abstract
The phenomenon of imbalance is a variation of voltage and current waveforms from a perfect sinusoidal waveform, which is considered a crucial challenge in power systems. Uneven loads and disturbances result in three‐phase voltage/current unbalance that leads to a temperature rise and low output curves at synchronous machines. Thus, the unbalance/fault must be recognized and avoided. This article suggests a methodology to detect and evaluate three‐phase voltage and current unbalance/fault using a coherence algorithm. The suggested scheme develops integrated protection functions that can be divided into three modules: voltage unbalance, current unbalance, and power factor unbalance. Therefore, it can be useful in mitigation techniques applied to compensate the voltage unbalance effects. The present protection introduces a new proposal of closed‐tripping curves based on the values range of nine coherence factors. To investigate the protection performance, a segment of power grid with real parameters’ information is simulated utilizing ATP platform. Several fault types, such as shunt and series faults, are conducted on the simulated system to analyze the results and monitor the system status using the coherence statistic processed in MATLAB software. The results show that the approach is smart, swift, precise, reliable and stable. Moreover, the algorithm can be practically implemented, and represents a base for digital unbalance/fault detectors and relays because its performance is superior in detecting Power Quality Disturbances (PQDs).Keywords
This publication has 20 references indexed in Scilit:
- Development and Analysis of a Sensitivity Matrix of a Three-Phase Voltage Unbalance FactorIEEE Transactions on Power Systems, 2018
- Power Quality Assessment of Different Load CategoriesEnergy Procedia, 2017
- Effect of voltage unbalance and distortion on the loss characteristics of three‐phase cage induction motorIET Electric Power Applications, 2017
- Real‐time cross‐correlation‐based technique for detection and classification of power quality disturbancesIET Generation, Transmission & Distribution, 2017
- Identification of coherency and critical generators set in real‐time signalIET Generation, Transmission & Distribution, 2017
- Application of fractional Fourier transform for classification of power quality disturbancesIET Science, Measurement & Technology, 2017
- Practical evaluation of unbalance and harmonic distortion in power conditioningElectric Power Systems Research, 2016
- Conjugate gradient back-propagation based artificial neural network for real time power quality assessmentInternational Journal of Electrical Power & Energy Systems, 2016
- Symmetrical Components-Based Modified Technique for Power-Quality Disturbances Detection and ClassificationIEEE Transactions on Industry Applications, 2016
- Intelligent fault diagnosis of synchronous generatorsExpert Systems with Applications, 2016