Assessment of the effect of structural and geophysical parameters on the magnetic field distribution around power lines located in underground collectors
Purpose. To quantitatively estimate the contribution of the surrounding-medium parameters to the magnetic flux density of a three-phase 110 kV air-insulated transmission line installed inside an underground tunnel, and to clarify whether such parameters must be included in routine engineering magnetic-field assessments. Methodology. Numerical quasi-stationary simulation of the magnetic field at industrial frequency was carried out for a symmetric three-phase system of AC-240/32 conductors loaded with 500 A. The computational domain was decomposed into five characteristic horizontal layers extending from the open air above the ground surface to the very plane of the phase wires. Two parametric series were performed: in the first the soil resistivity was scanned from 50 to 1000 Ω·m at a fixed wall thickness; in the second the concrete-wall thickness was varied from 250 to 500 mm at a fixed soil resistivity of 70 Ω·m. Findings. Within the studied envelope of parameters neither the resistivity of the soil nor the thickness of the concrete wall measurably alters the magnetic flux density either at the control point or inside any of the analyzed layers. The configuration of the field is governed almost exclusively by the magnitude of the phase current and by the geometry of the conductor cluster. At the reference point the peak flux density is approximately 1.5 μT and is reached at phase angles of about 115° and 295°; the value rises to roughly 2.27 μT at the ground surface, to about 8 μT on the upper outer face of the tunnel and exceeds 10 μT on its inner face, while pronounced local maxima are observed in the immediate vicinity of the individual phase wires. Originality. A systematic quantitative demonstration is provided that for a 110 kV underground concrete collector in typical urban operating conditions the soil and the reinforced-concrete envelope contribute negligibly to magnetic-field attenuation at 50 Hz. The widespread informal design assumption about the natural shielding role of these media is therefore not supported within the considered ranges of parameters. Practical value. The reported results allow designers to omit detailed soil and concrete characterization from preliminary magnetic-field calculations above underground collectors and to instead direct mitigation efforts toward optimization of phase-conductor geometry or toward dedicated active and passive shielding solutions, the only practically effective routes to a noticeable reduction of magnetic flux density in compact underground transmission infrastructure.