Abstract
Accurate transmission line representation is essential for reliable hardware validation and quasi-dynamic assessment of powersystem flexibility under high PV penetration. This study experimentally validates a physical Lucas-Nülle 300 km three-phase transmission line model and subsequently applies its equivalent electrical parameters in quasi-dynamic power-flow simulations. Three software representations (lumped-series, nominal-π and distributed-parameter models) are evaluated against the physical benchmark under resistive and inductive loading. The lumped-series provides the closest agreement, with an average receiving-end voltage error of 2.0 V, whereas nominal-π overestimate voltage by 4.7V to 6.7 V. Distributed parameter model exhibit larger deviations, with an average error of 14.2 V. These results establish the lumped-series as the most suitable electrical representation of the physical benchmark for subsequent software model application. The physical model is then represented in DIgSILENT PowerFactory as both 300 km transmission line and a three-bus ring network. The Newton–Raphson method is used to solve the quasi-dynamic power flow, with solar PV generation and data-center load profiles incorporated as time-varying inputs. The normal load profile results reveal substantial temporal grid-power variations, with maximum external grid supply of 22.35MW and 37.70MW absorption and peak net load ramp of 4.55MW/5min. The corresponding energy shifting requirement is 162.4 MWh. For the data-center load, the minimum design requirements include a ramp rate of 9.71MW/5min, power rating of 18.07MW and balancing energy of 96.63 MWh. The results establish a systematicpathway from experimental transmission line validation to system-level quasi-dynamic simulation for quantifying flexibility in solar PV power systems and supporting future hardware-in-the-loop studies.