Resonance Behavior and Sensitivity to Detect Mechanical Change in Transformer Winding: Shunt Current Versus Neutral Current
Author:
- 29 April 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 30 (5) , 2276-2283
Abstract
Frequency-response measurement offers by far the most sensitive known technique to detect any mechanical deformation in transformer windings. By default, during this measurement, the neutral or line current is considered as the winding response. The overall sensitivity to detect a mechanical change depends not only on the response quantity and the terminal connections chosen, but, also on the arrangement of poles and zeros of the system function. Some pole-zero arrangements are inherently better suited to reveal mechanical changes. Because of this, it is imperative to examine whether neutral current is indeed the best response quantity to consider or if there exists any other quantity, say, for example, total shunt current of the winding (also referred to as the tank current), to accomplish this task better. With this motivation, this paper compares the resonance behavior of neutral and tank current. Based on analytical derivations and actual experiments, it emerges that for detecting simulated mechanical changes, the tank current seems to be a more competent alternative compared to neutral current. It offers enhanced detection sensitivity, especially for interleaved windings. The possible reasons to explain why it is so are presented. The author believes that this finding needs reinforcement by field trials to ascertain its viability.Keywords
This publication has 12 references indexed in Scilit:
- Detection of Failures Within Transformers by FRA Using Multiresolution DecompositionIEEE Transactions on Power Delivery, 2014
- A new diagnostic method to support standard frequency response analysis assessments for diagnostics of transformer winding mechanical failuresIEEE Electrical Insulation Magazine, 2014
- Enhancing physical resolution of constructed ladder network for an interleaved winding2013
- Construction of Physically Realizable Driving-Point Function From Measured Frequency Response Data on a Model WindingIEEE Transactions on Power Delivery, 2008
- Identification of Terminal Connection and System Function for Sensitive Frequency Response Measurement on TransformersIEEE Transactions on Power Delivery, 2008
- Winding movement in power transformers: a comparison of FRA measurement connection methodsIEEE Transactions on Dielectrics and Electrical Insulation, 2006
- Impedances for the calculation of electromagnetic transients within transformersIEEE Transactions on Power Delivery, 2002
- Studies on impulse behaviour of a transformer winding with simulated faults by analogue modellingIEE Proceedings - Generation, Transmission and Distribution, 1994
- Impulse testing of power transformers using the transfer function methodIEEE Transactions on Power Delivery, 1988
- Transformer Diagnostic Testing by Frequuency Response AnalysisIEEE Transactions on Power Apparatus and Systems, 1978