This paper proposes a general approach for voltage-quality regulation. The same framework covers voltage-amplitude variations, dips, and swells. The framework uses the difference between power-quality events and power-quality variations to introduce a ldquoresponsibility-sharing curverdquo distinguishing between normal operational voltage for which equipment should be immune and events that are subject to voltage-quality regulation. It is further proposed to use equipment immunity requirements as a basis for the responsibility-sharing curve.