Abstract
When asymmetrical faults occur in power grid utilizing STATCOM, negative-sequence current should be intentionally injected to support the grid or compensate unbalanced load. However, the extreme compensation range of negative-sequence current injection becomes complicated when grid voltage becomes asymmetrical. This paper proposes a novel scheme for negative-sequence current compensation under two typical kinds of asymmetrical grid faults single-phase voltage drop and double-phase voltage drop. The proposed method has the following two benefits simultaneously: compensating as much negative current as possible, avoiding huge amount of calculation. In this paper, the mechanism of phase-to-phase DC voltage balancing in STATCOM is analyzed and a new identification method of negative-sequence current compensation range is explored out. To simplify the calculation, the ratio of negative-sequence reactive (Iq-) and active (Id-) current is taken as a variable (s), and then the relationship between the extreme compensation range and asymmetrical voltage sag depth (h) is drawn with MATLAB. Instead of conventional iterative method, the identification method uses curve fitting to approximate the accurate ranges of negative-sequence current compensation under different asymmetrical grid faults as simple polynomials, significantly reducing the computation burdens. Simulation and experimental results verify the practicability of the proposed compensation method.