Abstract
Distance relays exhibit delayed operation for faults occurring near both ends of a transmission line. Numerous accelerated trip (AT) solutions have been introduced to address this limitation, including pilot and non-pilot types. Non-pilot methods are receiving particular attention due to their independence from communication infrastructure. However, the effectiveness of these methods is limited in the presence of inverter-based resources (IBRs), as their fault responses differ substantially from those of synchronous generators. This paper proposes a novel non-pilot AT scheme for distance relays, tailored explicitly for line-to-line and line-to-line-to-ground faults in IBR-integrated networks. At its core lies an innovative fault-location approach for pre- and post-remote circuit breaker operation (RCBO) conditions. The approach depends solely on locally measured voltage and current signals and is inherently insensitive to the fault current characteristics. By utilizing the estimated fault locations and their variations, the proposed scheme detects RCBO and issues either an accelerated or a time-delayed trip command. Extensive simulations in PSCAD/EMTDC under diverse fault and system conditions validate its fault location accuracy, significantly reduced fault-clearing time, and robustness against the distinctive behavior of IBRs.