MMC‐HVDC AC side line protection based on positive sequence fault component current ratio
Authors:
Open Access
- 22 September 2023
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 17 (19) , 4375-4385
Abstract
The high‐voltage direct current (HVDC) transmission based on modular multilevel converter shows the weak feed characteristic of limited fault current amplitude when connected to the traditional AC power grid, which leads to the risk of sensitivity reduction or even failure of the traditional pilot protection. Here, a modular multi‐level converter (MMC)‐HVDC AC side transmission line protection scheme based on positive sequence fault component current ratio is proposed. The positive sequence fault component current of the MMC‐HVDC side is calculated by using the positive sequence fault component current of the power grid side, and the fault is identified through the significant difference between the ratio of the positive sequence fault component current of the MMC‐HVDC side and the actual positive sequence fault component current of the MMC‐HVDC side in the case of internal and external faults. This method has the advantages of simple principle, low requirement for synchronous data, not affected by capacitive current and strong resistance to high resistance. The simulation results show that the algorithm can correctly partition internal and external faults, and is not affected by fault location, fault type and operation mode of converter station, and has high sensitivity and reliability.Keywords
All Related Versions
Funding Information
- National Natural Science Foundation of China (U22B6006)
This publication has 25 references indexed in Scilit:
- Performance evaluation of distance protection of transmission lines connected with VSC-HVDC system using closed-loop test in RTDSElectric Power Systems Research, 2017
- Effects of VSC based HVDC system on distance protection of transmission linesInternational Journal of Electrical Power & Energy Systems, 2017
- Improved differential current protection scheme for CSC‐HVDC transmission linesIET Generation, Transmission & Distribution, 2017
- Current differential protection principle of HVDC transmission systemIET Generation, Transmission & Distribution, 2017
- Arm Current Control Strategy for MMC-HVDC Under Unbalanced ConditionsIEEE Transactions on Power Delivery, 2016
- Fault detection in Multi-Terminal Modular Multilevel Converter (MMC) based High Voltage DC (HVDC) transmission system2015
- Analysis of the Performance of MMC Under Fault Conditions in HVDC-Based Offshore Wind FarmsIEEE Transactions on Power Delivery, 2015
- A Postfault Strategy to Control the Modular Multilevel Converter Under Submodule FailureIEEE Transactions on Power Delivery, 2015
- Nonunit Protection of HVDC Grids With Inductive DC Cable TerminationIEEE Transactions on Power Delivery, 2015
- Multi-terminal VSC HVDC for the European supergrid: ObstaclesRenewable and Sustainable Energy Reviews, 2010