Performance testing of engineering controls of airborne infection isolation rooms by tracer gas techniques
- 2 August 2013
- journal article
- Published by SAGE Publications in Indoor and Built Environment
- Vol. 23 (7) , 994-1001
Abstract
The ventilation performance of airborne infection isolation rooms (AIIRs) was assessed in three Finnish hospitals by examining the air change rate, contaminant removal efficiency and leakage of contaminants outside the isolation room by using tracer gas techniques. Results showed that infectious agents can escape from the AIIR during egress despite high ventilation rates in the AIIR and anteroom (air change rate, 4–24 h−1) and the pressure difference between the AIIR and corridor was −0.2 to −29 Pa. The control of impurities was often ineffective due to inappropriate direction of air flows and air moving from the patient towards the health care worker and anteroom. Although an anteroom reduces leakage of infectious agents to the corridor significantly, it does not prevent this completely when healthcare workers move between the AIIR and corridor. To enhance the protection of AIIRs, it is especially important to pay attention to the air distribution and removal efficiency of impurities in AIIRs and anterooms. Performance of AIIRs should be tested regularly, especially among older AIIRs.Keywords
This publication has 19 references indexed in Scilit:
- An Evaluation of the Ventilation Performance of New SARS Isolation Wards in Nine Hospitals in Hong KongIndoor and Built Environment, 2007
- A performance assessment of airborne infection isolation roomsAmerican Journal of Infection Control, 2007
- Role of ventilation in airborne transmission of infectious agents in the built environment ? a multidisciplinary systematic reviewIndoor Air, 2007
- Containment testing of isolation roomsJournal of Hospital Infection, 2004
- A Simple Method for Tracer Containment Testing of Hospital Isolation RoomsApplied Occupational and Environmental Hygiene, 2002
- An Evaluation of Hospital Special-Ventilation-Room PressuresInfection Control & Hospital Epidemiology, 2001
- Identification of Factors That Disrupt Negative Air Pressurization of Respiratory Isolation RoomsInfection Control & Hospital Epidemiology, 2000
- Evaluating the Control of Tuberculosis among Healthcare Workers: Adherence to CDC Guidelines of Three Urban Hospitals in CaliforniaInfection Control & Hospital Epidemiology, 1998
- Follow-up Evaluation of Respiratory Isolation Rooms in 10 Midwestern HospitalsInfection Control & Hospital Epidemiology, 1996
- Evaluation of Rooms with Negative Pressure Ventilation Used for Respiratory Isolation in Seven Midwestern HospitalsInfection Control & Hospital Epidemiology, 1993