Impact of oil velocity on partial discharge characteristics induced by bubbles in transformer oil
- 8 October 2018
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 25 (5) , 1605-1613
Abstract
Bubble is a typical insulation defect in transformer oil, which can easily initiate partial discharge (PD) during the operation of transformer. Moreover, it migrates along with the oil flow and may be deformed due to the forced oil circulation and temperature difference within transformer bulk, leading to the complexity of PD characteristics and PD mechanism. However, the understanding of to this phenomenon is not clear. In order to identify it, finite element method was employed to simulate the movement process and deformation of bubbles, as well as electric field distribution under the conditions with different oil flow rates. In addition, numerous experiments were performed, mainly including the change of PD ϕ-q and ϕ-n patterns with oil flow rates. By comparing the simulation and experimental results, it is found that PDs are mainly concentrated in the negative half-cycle. Electric force causes bubbles to stretch along the electric field direction. At the stationary condition, bubbles eventually exhibit horizontal stretching and cause maximum electric field distortion. However, bubbles eventually exhibit vertical stretching in flowing oil. Flowing oil can significantly reduce PD intensity. The PD intensity declines rapidly with the increase of the flow velocity, and then increases slowly.Keywords
This publication has 19 references indexed in Scilit:
- Investigation of partial discharge between moving charged metal particles and electrodes in insulating oil under flow state and AC conditionIEEE Transactions on Dielectrics and Electrical Insulation, 2016
- Modeling of early stage partial discharge and overheating degradation of paper-oil insulationIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- An investigation of behaviours of a single bubble in a uniform electric fieldExperimental Thermal and Fluid Science, 2006
- PD Pulse Burst Characteristics of Transformer OilsIEEE Transactions on Power Delivery, 2006
- A diffuse-interface method for simulating two-phase flows of complex fluidsJournal of Fluid Mechanics, 2004
- Thermally and electrically induced bubbles in liquid argon and nitrogenIEEE Transactions on Dielectrics and Electrical Insulation, 2002
- Phase relationship of PD pulses in dielectric liquids under ac conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 2000
- Simultaneous ultrawide and narrowband detection of PD pulses in dielectric liquidsIEEE Transactions on Dielectrics and Electrical Insulation, 1998
- Partial discharge distributions in liquid dielectricsIEEE Transactions on Electrical Insulation, 1992
- Prebreakdown density change, current and light emission in transformer oil under non-uniform fieldJournal of Electrostatics, 1982