For a long time, the identification of 10kV distribution network line loss anomalies has been a very difficult task, with the large number of distributed photovoltaics (DPV) access, the distribution network power flow from one-way flow to two-way flow, which greatly affects the line power flow, voltage and network loss, and increases the difficulty of identifying abnormal distribution network line loss. Therefore, a method for identifying line loss anomalies in distribution network considering distributed photovoltaic access is proposed. Firstly, the characteristic index of distribution network line loss after distributed photovoltaic access is extracted, and the correlation between the line loss index and line loss of the distribution network is calculated by using the gray correlation analysis method, and the correlation degree is ranked. Then, according to the order of gray correlation degree, appropriate indicators are selected for fuzzy C-means clustering, and outliers in each category are detected based on the K-nearest neighbor algorithm to determine whether there is an abnormal line loss in the distribution network. Finally, the verification analysis is carried out through the example, and the results show that the proposed method can effectively identify whether abnormal line loss occurs in the distribution network containing distributed photovoltaics.