Establishment and Application of 1200-kV Lightning Impulse Voltage Reference Measuring System
Open Access
- 11 November 2025
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 74 (00189456) , 1-10
Abstract
The National Metrology Institute (NMI) of The Netherlands (VSL) developed a new 1200-kV reference measuring system for on-site calibration of lightning impulse (LI) voltage measuring systems. Improvement of the low-voltage grounding loop and triaxial signal transmission reduced oscillation ripples and enhanced the shielding of environmental high-frequency interference. Calibration and measurement capabilities are realized in the test voltage ( ${U}_{t}$ ), front time ( ${T}_{1}$ ), and time to half-value ( ${T}_{2}$ ) with uncertainties of 0.7%, 3.0%, and 1.5%, respectively, up to 600 kV and 1.2%, 5.0%, and 3.0%, respectively, up to 1200 kV for direct comparison calibration. With additional linearity experiments, VSL is now able to provide LI voltage calibrations on-site up to 3000 kV. The VSL system was used as the reference for calibration and tuning of a 4000-kV LI divider to improve its accuracy performance. A measurement campaign was held to compare different LI measuring systems and research the linearity of the measuring system up to 3000 kV. The comparison results confirmed the good performance of the VSL 1200-kV reference measuring system and also indicated that the 4000-kV measuring system was improved after calibration and tuning with the VSL reference system.Keywords
Funding Information
- European Metrology Program for Innovation and Research co-financed by the Participating States and in part by European Union’s Horizon 2020 Research and Innovation Program
This publication has 14 references indexed in Scilit:
- Linearity extension of UHV class lightning impulse dividers up to 3000 kVIET Conference Proceedings, 2025
- VSL 1200 kV Reference Measuring System for Lightning Impulse Voltage Calibrations2024
- Calibration and Fine-Tuning of a 4000 kV Lightning Impulse Generator Circuit and Divider2024
- Supplementary comparison EURAMET.EM-S42, comparison of lightning impulse (LI) reference measuring systemsMetrologia, 2020
- High Impulse Voltage and Current Measurement Techniques2013
- Worldwide Comparison of Lightning Impulse Voltage Measuring Systems at the 400-kV LevelIEEE Transactions on Instrumentation and Measurement, 2007
- Fast resistive attenuators for high accuracy measurements of LI voltages2004
- Uncertainties of impulse voltage measurements at NML, CSIRO and INMS, NRC2003
- A calculable impulse voltage calibrator for calibration of impulse digitizersIEEE Transactions on Instrumentation and Measurement, 2003
- Precision digital filters for high voltage impulse measurement systemsIEEE Transactions on Power Delivery, 1999