Travelling waves‐based identification of sub‐health condition of feeders in power distribution system
Authors:
Open Access
- 24 January 2018
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 12 (5) , 1067-1073
Abstract
The majority of faults in power distribution system are caused by natural degradation of feeders. In addition, travelling waves will be generated during degradation of feeders. This study proposes a method based on travelling waves to identify sub‐health condition, which represents the degradation of feeder before the feeder fails into a permanent fault. In the method, traveling waves in the power distribution system are monitored in real time. Then, the location of travelling wave source is determined by the polarity of travelling waves, which is extracted using wavelet transform. Finally, the degradation of feeder is identified when all the other possibilities to generate travelling waves are ruled out using the characteristics of power‐frequency voltages and currents accompanied with travelling waves. Simulation results have verified that the proposed method is feasible and effective.Keywords
Funding Information
- National Natural Science Foundation of China (51120175001)
This publication has 13 references indexed in Scilit:
- Traveling‐wave‐based protection of parallel transmission lines using Teager energy operator and fuzzy systemsIET Generation, Transmission & Distribution, 2016
- Kalman filter based incipient fault detection method for underground cablesIET Generation, Transmission & Distribution, 2015
- Application of Waveform Analytics for Improved Situational Awareness of Electric Distribution FeedersIEEE Transactions on Smart Grid, 2015
- Incipient Fault Location Algorithm for Underground CablesIEEE Transactions on Smart Grid, 2014
- Time–time‐transform‐based fault location algorithm for three‐terminal transmission linesIET Generation, Transmission & Distribution, 2013
- Intelligent Systems for Improved Reliability and Failure Diagnosis in Distribution SystemsIEEE Transactions on Smart Grid, 2010
- Detection of Incipient Faults in Distribution Underground CablesIEEE Transactions on Power Delivery, 2010
- A Novel Condition Assessment System for Underground Distribution ApplicationsIEEE Transactions on Power Systems, 2009
- Evaluation of Feeder Monitoring Parameters for Incipient Fault Detection Using Laplace Trend StatisticIEEE Transactions on Industry Applications, 2004
- Identification of symptom parameters for failure anticipation by timed-event trend analysis [power distribution systems]IEEE Power Engineering Review, 2000