Abstract
Building performance simulation inherits internal heat gain schedules from datasets assembled almost entirely in North American and European housing. Global South housing departs from those antecedents, so inherited schedules can misstate the dwellings they describe. This paper quantifies one such load: the Mitad, the electric injera cooker used in most Ethiopian households. Evidence comes from 48 households in Addis Ababa condominium housing: 3,584 diary entries, 20 key-informant interviews, four focus groups, and a four-stage EnergyPlus calibration against ASHRAE Guideline 14. The Mitad dissipates 2,000 W into kitchens of roughly 20 m³ in 83.3% of households for a mean of 72 minutes each evening. Under security-constrained ventilation, calibrated models place the kitchen 5.8 °C above the living room during operation and 2.4 °C an hour later, and evenings with baking are 0.41 points warmer than baking-free evenings within the same household (p < .001, d = 0.68). Incorporating the load as a zone-level scheduled gain cut mean bias error from -30.0% to -7.5% and the coefficient of variation of the root-mean-square error from 31% to 24%, within Guideline 14 limits. Because injera preparation is culturally non-negotiable, the findings support ventilation-first design and a five-step protocol for other culturally embedded cooking loads.