Abstract
As the penetration of inverter-based resources increases rapidly, the power system's transient stability is facing severe challenges. Grid-forming converters (GFMC) with voltage–frequency support capability are in urgent need of investigation. Conventional power-synchronization-based GFMCs need a constant dc-link voltage (DV), which is not always available. DV synchronization control (DVSC) that can spontaneously maintain constant DV has better adaptability in practice. However, the transient stability of DVSC-based GFMC is relatively complicated and has been rarely studied due to its frequency-related varying inertia and internal voltage. In this article, the kinetic and potential energies of DVSC-based GFMC are analytically deduced, which captures the impact of frequency-related varying inertia and internal voltage. Based on the equal area criterion, the transient stable boundary of DVSC-based GFMC is accurately quantified through an iterative method. Further, the influence of different control parameters on transient stability is revealed. Experimental results verify the effectiveness of the transient stability analysis results.
Funding Information
  • National Natural Science Foundation of China (52222707)
  • National Natural Science Foundation of China (52437009)
  • National Natural Science Foundation of China (52477195)

This publication has 44 references indexed in Scilit: