Limiting surge arrester failure under direct lightning strokes for attaining service continuity of distribution networks
Open Access
- 9 September 2020
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 14 (21) , 4796-4804
Abstract
This study introduces an arrangement of surge arrester, Rogowski coil, and triac to attain service continuity of distribution networks. This new arrangement is proposed to limit the arrester failure due to lightning flashes striking distribution feeders. The arrester failure is probably happened due to the increase of absorbed energy over the withstand capability. As the lightning flash has multiple discharges, an equivalent single wave model is computed to evaluate the arrester discharge energy. The arrester discharge current is monitored using a single Rogowski coil. Then, the arrester's dynamic characteristic (current–voltage) is utilised to estimate the discharge energy using only the arrester current. The arrester and associated Rogowski coil are distributed in an 11 kV distribution network. Due to travelling‐waves reflections of the direct lightning striking the distribution feeder, the discharge energy of the installed arresters in the network is different than the computed energy using the lightning flash current as an impulse current source directly applied on the arrester device. Finally, the parallel triac with the arrester is suggested and triggered for limiting the arrester's failure. The detailed model of this proposed arrangement is evaluated via an electromagnetic simulation software. The failure assessment is statistically evaluated using the MATLAB software.Keywords
This publication has 34 references indexed in Scilit:
- Evaluation of lightning-related faults that lead to distribution network outages: An experimental case studyElectric Power Systems Research, 2019
- Measurement of Lightning-Induced Overvoltage in Power Distribution Lines Using Ceramic-Capacitor InsulatorIEEE Transactions on Electromagnetic Compatibility, 2019
- Application possibilities of special lightning protection systems of overhead distribution and transmission linesInternational Journal of Electrical Power & Energy Systems, 2018
- Response of distribution networks to direct and indirect lightning: Influence of surge arresters location, flashover occurrence and environmental shieldingElectric Power Systems Research, 2017
- Evaluation of Power System Lightning Performance—Part II: Application to an Overhead Distribution NetworkIEEE Transactions on Electromagnetic Compatibility, 2016
- Probabilistic Risk Assessment of MV Insulator Flashover Under Combined AC and Lightning-Induced OvervoltagesIEEE Transactions on Power Delivery, 2015
- Effect of the grounding resistance to the behaviour of high‐voltage transmission lines’ surge arrestersIET Science, Measurement & Technology, 2014
- An improvement for the selection of surge arresters based on the evaluation of the failure probabilityIEEE Transactions on Power Delivery, 2002
- Transmission line arrester energy, cost, and risk of failure analysis for partially shielded transmission linesIEEE Transactions on Power Delivery, 2000