Impact of distributed single-phase rooftop solar inverter clusters on negative sequence voltage and neutral conductor loading in low-voltage distribution feeders
Unbalanced single-phase solar generation is already the dominant source of negative sequence voltage in many residential low-voltage networks, yet the quantitative relationship between rooftop photovoltaic penetration and neutral conductor thermal loading remains poorly mapped under field conditions. This research measured voltage unbalance factor and neutral current on two 400 V feeders in Wollongong, Australia, across fifteen progressive solar penetration levels ranging from 6% to 92% of transformer rating. A three-month monitoring campaign between June and August 2024 captured 10-minute averaged data from power quality recorders installed at the transformer secondary and at three downstream nodes on each feeder. The voltage unbalance factor exceeded the 2% limit specified by AS/NZS 61000.2.2 at solar penetration above 72% on Feeder A and above 64% on Feeder B, where inverter allocation was more asymmetric. Neutral conductor current reached 68.3% of phase conductor rating at 92% penetration on Feeder B, raising the joule loss in the neutral by a factor of 4.7 relative to the no-solar baseline. A strong linear correlation (r = 0.989 to 0.993, P < 0.001) was found between solar penetration and voltage unbalance factor on both feeders. Results show that phase-balancing controls embedded in smart inverter firmware can hold the voltage unbalance factor below 1.2% up to 85% penetration, provided no single phase carries more than 40% of the total installed capacity.